Data from Influence of Fire on the Lateral Resistance of Cold-Formed Steel Shear Walls - Phase 2

收藏
NIST Chemistry WebBook2026-03-14 收录
下载链接:
https://www.nist.gov/el/fire-research-division-73300/national-fire-research-laboratory-73306/influence-fire-lateral-0
下载链接
链接失效反馈
官方服务:
资源简介:
Twenty-two 2.7 m by 3.7 m shear wall specimens consisting of 150 mm wide CFS framing were tested. All walls were designed to achieve a 1-hour fire-resistance rating per American Society for Testing and Materials (ASTM) standard E119. Heating was applied to the side of the wall opposite to the side where the shear-resisting elements are located; it is assumed that the shear-resisting elements line an egress corridor and the fire occurs in a room adjacent to the corridor. The walls are designed using Allowable Stress Design nominally following American Iron and Steel Institute (AISI) standards S400-15/S1-16 and AISI S100-16.