The Experimental Setup Data Set
收藏Figshare2025-09-01 更新2026-04-08 收录
下载链接:
https://figshare.com/articles/dataset/The_Experimental_Setup_Data_Set/30024013/1
下载链接
链接失效反馈官方服务:
资源简介:
High peak-hour energy consumption from air conditioning in commercial buildings creates significant operational costs and grid instability. This study experimentally investigates the thermo-economic performance of a vapor compression refrigeration system (VCR) ice storage system to address this challenge through load-shifting. The methodology involved operating a custom test rig, featuring an insulated test chamber and an ice tank with a novel spiral evaporator, under an improved 8-hour night charging and 9-hour day discharge strategy. Results show the system consumed 5.44 kWh of electricity to store 7.70 kWh of thermal energy, achieving a charging Coefficient of Performance (COP) of 1.42. A total of 5.195 kWh of cooling was delivered with a discharge efficiency of 67.5%. The experimental cost analysis confirmed an approximate 20% operating cost advantage over conventional direct cooling. A simple payback assessment indicates strong sensitivity to tariff structures and annual operating days. This study concludes that the optimized Ice Storage System (ISS) is a technically viable and economically advantageous solution for managing peak cooling loads, providing a validated reference model and dataset for future work.
提供机构:
Ergün, Enes
创建时间:
2025-09-01



