Studies on coiled wire finned heat exchangers operating with wide boiling mixtures.

收藏
DataCite Commons2020-09-18 更新2025-04-16 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0015276&DOCBASE=IFD_REFDOC_EN&SETLANGUAGE=EN
下载链接
链接失效反馈
官方服务:
资源简介:
Heat exchanger effectiveness of more than 90% is required for a J-T refrigerator to function when nitrogen is used as the refrigerant and over 95% when mixtures are used as the refrigerant. Coiled wire finned heat exchangers with effectiveness greater than 97% have been built and tested in our laboratory for use in J-T refrigerators operating with mixtures. Experiments have been conducted on prototype heat exchanger with a nitrogen-hydrocarbon mixture and temperature of the shell measured at some locations. The measured temperatures are compared with some single and two-phase heat transfer coefficient estimation methods available in the literature.