Data from Influence of Fire on the Lateral Resistance of Cold-Formed Steel Shear Walls - Phase 2
收藏DataCite Commons2021-03-18 更新2025-04-16 收录
下载链接:
https://www.nist.gov/el/fire-research-division-73300/national-fire-research-laboratory-73306/influence-fire-lateral-0
下载链接
链接失效反馈官方服务:
资源简介:
Twenty-two 2.7 m by 3.7 m shear wall specimens
consisting of 150 mm wide CFS framing were tested. All walls were designed to achieve a 1-hour
fire-resistance rating per American Society for Testing and Materials (ASTM) standard E119.
Heating was applied to the side of the wall opposite to the side where the shear-resisting
elements are located; it is assumed that the shear-resisting elements line an egress corridor
and the fire occurs in a room adjacent to the corridor. The walls are designed using Allowable
Stress Design nominally following American Iron and Steel Institute (AISI) standards
S400-15/S1-16 and AISI S100-16.
提供机构:
National Institute of Standards and Technology
创建时间:
2019-04-08