Concept and calculation method of local cooling/heating load applied to non-uniform indoor environment.
收藏Mendeley Data2023-09-19 更新2024-06-27 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0015997&DOCBASE=IFD_REFDOC&SETLANGUAGE=FR
下载链接
链接失效反馈官方服务:
资源简介:
Traditionally, the definition and calculation of room load is based on the assumption that indoor environment is mixed uniformly. Actually, the indoor environment is non-uniform and only one or some local zones need to be controlled. In order to calculate the cooling/heating load in anon-uniform indoor environment, a new concept, Local Cooling/Heating Load (LC/HL), is proposed in the paper. An office room with two kinds of air distribution systems and two kinds of heat sources distribution is adopted to demonstrate and discuss the LC/HL with CFD tool. The results show that the LC/HL can be greater or less than the whole room load, which depends on the air distribution and the heat sources distribution.