five

Experimental study on diffusion absorption refrigeration cycle using low GWP refrigerants.

收藏
DataCite Commons2020-09-20 更新2025-04-16 收录
下载链接:
http://iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0024812&DOCBASE=IFD_REFDOC_EN&SETLANGUAGE=EN
下载链接
链接失效反馈
官方服务:
资源简介:
Compared to the conventional absorption refrigeration systems, diffusion absorption refrigeration (DAR) system consists of three components of the working fluids: refrigerant, absorbent, and auxiliary gas. In general, the DAR uses ammonia and water as the working fluids. However, ammonia is flammable, explosive, toxic, and d by high pressure gas safety management act. The main objective of this study is to select a low GWP refrigerant, its pair absorbent and auxiliary gas by experimental investigation. During the experiments, types of the refrigerant-absorbent pair, concentration of the refrigerant, pressure, and temperature are considered as the key parameters to obtain the maximum coefficient of performance (COP) and a low evaporation temperature. The optimum conditions for the key parameters were determined by experiments. It was found that R1234ze(E) gave the best COP with the evaporation temperature of -12.2 oC.
提供机构:
International Institute of Refrigeration (IIR)
创建时间:
2018-11-19
5,000+
优质数据集
54 个
任务类型
进入经典数据集
二维码
社区交流群

面向社区/商业的数据集话题

二维码
科研交流群

面向高校/科研机构的开源数据集话题

数据驱动未来

携手共赢发展

商业合作