Indoor air quality in new and renovated lowâincome apartments with mechanical ventilation and natural gas cooking in California
收藏DataONE2020-10-23 更新2025-05-10 收录
下载链接:
https://search.dataone.org/view/sha256:49a75c34926183483011b3992f363734dd4e2e605fd046bb0b0559aad45baad9
下载链接
链接失效反馈官方服务:
资源简介:
This study presents pollutant concentrations and performance data for code-required mechanical ventilation equipment in 23 low-income apartments at 4 properties constructed or renovated 2013-2017. All apartments had natural gas cooking burners. Occupants pledged to not use windows for ventilation during the study but several did. Measured airflows of range hoods and bathroom exhaust fans were lower than product specifications. Only eight apartments operationally met all ventilation code requirements. Pollutants measured over one week in each apartment included time-resolved fine particulate matter (PM2.5), nitrogen dioxide (NO2), formaldehyde and carbon dioxide (CO2) and time-integrated formaldehyde, NO2 and nitrogen oxides (NOX). Compared to a recent study of California houses with code-compliant ventilation, apartments were smaller, had fewer occupants, higher densities, and higher mechanical ventilation rates. Mean PM2.5, formaldehyde, NO2, and CO2 were 7.7 µg/m3, 14.1 ppb, 18.8 ppb,...
创建时间:
2025-04-25