five

(Data alongside) Fault prediction of gas-insulated system with hypersensitive optical monitoring and spectral information

收藏
Mendeley Data2026-04-18 收录
下载链接:
https://data.mendeley.com/datasets/xncfcdsyj7
下载链接
链接失效反馈
官方服务:
资源简介:
Fig. 1. Phase-resolved scatterplots (φ, q), double-spectral scatterplots (Iband1, Iband2) for corona discharges occurring along the needle-plane gaps with different gap distances (d). (a)-(c): (φ, q); (d)-(f): (Iband1, Iband2); Fig. 2. Integral spectra of the corona discharge in SF6 (gap distance = 50 mm; gas pressure = 0.3 MPa; f = 15). A fiber-optic spectrometer (200-1150 nm), a collecting lens installed outside the quartz glass window of the test chamber, and a 19-core silica fiber were employed to measure the integral spectra of the discharges. Fig. 7. Light intensity stochastic distributions in an RGB 3-D coordinate system for the three types of defect. Fig. 11. Scatterplots of the DBSCAN clustering results for a double-sourced discharge (floating discharge and creeping discharge occur simultaneously with a discharge level of 320 pC). Fig. 15. Results of clustering analysis on TSS data (Cluster 1 and Cluster 2) and the evolution paths of the two types of discharge (Corona discharge: 30 μJ→93 μJ; Floating discharge: 77 μJ→224 μJ).
创建时间:
2019-12-29
5,000+
优质数据集
54 个
任务类型
进入经典数据集
二维码
社区交流群

面向社区/商业的数据集话题

二维码
科研交流群

面向高校/科研机构的开源数据集话题

数据驱动未来

携手共赢发展

商业合作