Experimental Research on the Pull-Out Performance of FRP Bar Connectors Considering Concrete Age

收藏
中国科学数据2026-03-18 更新2026-04-25 收录
下载链接:
https://www.sciengine.com/AA/doi/10.3724/j.gyjzG26012810
下载链接
链接失效反馈
官方服务:
资源简介:
To investigate the pull-out performance of FRP bar connectors during the construction stage, this study designed and conducted pull-out tests on four groups with a total of twelve FRP bar connectors, with concrete strength (C25, C15) and insulation layer thickness (50 mm, 70 mm) as the research parameters. The failure modes, pull-out bearing capacity, load-slip curves, and load-connector strain curves were systematically analyzed. The experimental results indicated that all specimens failed due to concrete anchorage failure at the connector end. Concrete strength grade had a significant influence on the pull-out bearing capacity of the connectors. When the concrete strength increased from C15 to C25, the pull-out bearing capacity of specimens with insulation layer thicknesses of 50 mm and 70 mm improved by 18.1% and 21.0%, respectively. In contrast, insulation layer thickness had a relatively minor effect on the pull-out bearing capacity. When the insulation layer thickness increased from 50 mm to 70 mm, the pull-out bearing capacity of specimens with concrete strength grades of C15 and C25 increased by 3.3% and 7.4%, respectively. At failure, the strain of the connectors along the pull-out direction remained well below the ultimate tensile strain of the FRP material, and no damage was observed in any of the connectors.