The effect of air purifiers and curtains on aerosol dispersion and removal in multi-patient hospital rooms

收藏
DataONE2022-07-26 更新2024-06-08 收录
下载链接:
https://search.dataone.org/view/sha256:70a89f30e2fc3a892cdb0054f4c95cf6379e6b89f6fc4326aec7f254b9dd6125
下载链接
链接失效反馈
官方服务:
资源简介:
Airborne transmission of disease is of concern in many indoor spaces. Here, aerosol dispersion and removal in an unoccupied 4-bed hospital room was characterized using a transient aerosol tracer experiment for 38 experiments covering 4 configurations of air purifiers and 3 configurations of curtains. NaCl particle (mass mean aerodynamic diameter ∼3μm) concentrations were measured around the room following an aerosol release. Particle transport across the room was 1.5 - 4 minutes which overlaps with the characteristic times for significant viral deactivation and gravitational settling of larger particles. Concentrations were close to spatially uniform except very near the source. Short curtains had no consistent effects on concentrations at the non-source patient locations while floor-length curtains reduced concentrations slightly depending on the purifier configuration. The aerosol decay rate was in most cases higher than expected from the clean air delivery rate, but the reduction in steady-state concentrations resulting from air purifiers was less than suggested by the decay rates. Apparently a substantial (and configuration-dependent) fraction of the aerosol is removed immediately and this effect is not captured by the decay rate. Overall, the combination of curtains and purifiers is likely to reduce disease transmission in multipatient hospital rooms.