Performance evaluation of a large capacity air-water heat pump using propane as refrigerant.
收藏DataCite Commons2020-09-18 更新2025-04-16 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0019024&DOCBASE=IFD_REFDOC_EN&SETLANGUAGE=EN
下载链接
链接失效反馈官方服务:
资源简介:
Heat pump applications working with hydrocarbons as refrigerant have been under significant development along with the gradual phasing-out of conventional HFC systems. In this study, a large capacity air-water heat pump prototype using propane as refrigerant is tested to evaluate its heating performance under different operating conditions. The experimental set-up is briefly explained. The results of the experimental investigations of the heat pump prototype are presented in terms of the COP1, heating capacity and the compressor efficiency. At the design point, the experimental COP1 and heating capacity are 3.43 and 36.59 kW respectively. Experimental results for all test conditions are compared to simulation results generated from the model, which is created by the software IMST-ART. The model is validated through comparisons of those parameters since a good agreement between simulated and experimental data have been found. The maximum discrepancies of COP1 and heating capacity are around 5% and 10% respectively.
提供机构:
International Institute of Refrigeration (IIR)
创建时间:
2016-12-21