five

CMU Wall Through-bolt Pushout

收藏
DataCite Commons2020-08-02 更新2025-04-16 收录
下载链接:
https://www.designsafe-ci.org/data/browser/public/nees.public/NEES-2010-0917.groups/Experiment-9
下载链接
链接失效反馈
官方服务:
资源简介:
Testing at the University of Hawaii @ Manoa as part of Project Task 2: Connector Development. This experiment is the second round of testing to establish the masonry capacity at through-bolt point loading. Steel link plates were slip-critically bolted to side plates, which were welded to a steel beam above the masonry wall specimens. A total of 11 reps were performed on 6 trial masonry wall specimens. In 5 of the specimens a single bolt was installed near the corner of the wall. Load was applied to the through-bolt toward the end of the wall until failure. The bond beam reinforcing and through-bolt location was varied from one rep to the next. For each of these five specimens, one rep tested the through-bolt at a distance of 12 inches from the end of the wall, the other rep tested the throughbolt located at 20 inches from the end of the wall. One of the specimens tested the effect of a 2 through-bolt group near the end of the wall: throughbolts were located at 12 inches and 28 inches from the end of the wall.
提供机构:
Network for Earthquake Engineering Simulation (NEES)
创建时间:
2013-12-03
5,000+
优质数据集
54 个
任务类型
进入经典数据集
二维码
社区交流群

面向社区/商业的数据集话题

二维码
科研交流群

面向高校/科研机构的开源数据集话题

数据驱动未来

携手共赢发展

商业合作