five

Priority Differentiation for Low-latency Smart Grid Communications in Wide Area Control

收藏
DataCite Commons2021-08-11 更新2025-04-16 收录
下载链接:
https://ieee-dataport.org/documents/priority-differentiation-low-latency-smart-grid-communications-wide-area-control
下载链接
链接失效反馈
官方服务:
资源简介:
Wide area control (WAC) in smart grid requires low-latency communications across the grid to transfer various control commands and Phasor Measurement Unit (PMU) measurements. \textcolor{red}{Smart grid communications are generally implemented between multiple control centers, between transformer substations and control centers, and between power plants and control centers}. While there have been a number of international standards for smart grid communications, detailed methods have not been specified in existing standards for low-latency transmission of different types of application data, particularly high-priority control commands, between control centers.To fulfill this requirement, a priority differentiation approach is presented in this paper for low-latency communications between control centers. With two application-layer queues, it incorporates a cross-layer design between the application layer and data-link layer to keep the delay of high-priority packets to the possible minimum. Simulation results in typical scenarios show a reduced communication latency of about 45\% for high-priority packets when our approach is incorporated with existing communication technologies.
提供机构:
IEEE DataPort
创建时间:
2021-08-11
5,000+
优质数据集
54 个
任务类型
进入经典数据集
二维码
社区交流群

面向社区/商业的数据集话题

二维码
科研交流群

面向高校/科研机构的开源数据集话题

数据驱动未来

携手共赢发展

商业合作