PV inverter experimental data
收藏DataCite Commons2023-01-24 更新2025-04-09 收录
下载链接:
https://www.osti.gov/servlets/purl/1914317/
下载链接
链接失效反馈官方服务:
资源简介:
The increase in power electronic based generation sources require accurate modeling of inverters. Accurate modeling requires experimental data over wider operation range. We used 20 kW off-the-shelf grid following PV inverter in the experiments. We used controllable AC supply and controllable DC supply to emulate AC and DC side characteristics. The experiments were performed at NREL's Energy Systems Integration Facility. Due to the limitations of the DC supply used, inverter is tested under 75%, 50%, 25% load conditions (This dataset does not contain 100% load condition). In the first dataset, for each operating condition, controllable AC source voltage is varied from 0.88 to 1.09 per unit (p.u) with a step value of 0.025 p.u while keeping the frequency at 60 Hz. In the second dataset, under similar load conditions (75%, 50%, 25% ), the frequency of the controllable AC source voltage was varied from 59.4 Hz to 60.45 Hz with a step value of 0.2 Hz. Voltage and frequency range is chosen based on inverter protection. Voltages and currents on DC and AC side are included in the dataset.
提供机构:
National Renewable Energy Laboratory - Data (NREL-DATA), Golden, CO (United States); National Renewable Energy Laboratory (NREL), Golden, CO (United States)
创建时间:
2023-01-24