five

Heat transfer coefficient of two-phase flow boiling with low vapor quality.

收藏
DataCite Commons2020-09-18 更新2025-04-16 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0015581&DOCBASE=IFD_REFDOC&SETLANGUAGE=FR
下载链接
链接失效反馈
官方服务:
资源简介:
The use of HCFCs refrigerants are gradually being replaced by HFCs and hydrocarbons refrigerants that has zero ODP (Ozone Depletion Potential). R-290 (propane) is a hydrocarbon refrigerant with C3H8 molecular structure. In this research, the flow boiling heat transfer occurs inside small tube with diameter of 7.6 mm and length of 1.07 m. In order to determine the value of heat transfer coefficient, the experiment were carried out for mass fluxes ranging from 200 kg/m2s to 400 kg/m2s, heat fluxes ranging from 5 kW/m2 to 20 kW/m2, and saturation temperatures from 5°C to 15°C. This study analyzed the heat transfer through the local heat transfer coefficient along the flow for low vapor quality region. The boiling heat transfer coefficient of R-290 is influenced by heat flux, mass flux, and saturation temperature. In comparison to previous boiling heat transfer correlations, the correlation of Shah (1982) best fitted the experimental result with the mean deviation of 32.20%. A new correlation for boiling heat transfer coefficient was developed by modification of F factor with regression method. The new correlation has smaller mean deviation of 22.46% in comparison with the present experimental result.
提供机构:
International Institute of Refrigeration (IIR)
创建时间:
2016-10-12
5,000+
优质数据集
54 个
任务类型
进入经典数据集
二维码
社区交流群

面向社区/商业的数据集话题

二维码
科研交流群

面向高校/科研机构的开源数据集话题

数据驱动未来

携手共赢发展

商业合作