five

Potential enhancement investigation of commercial R744 refrigeration systems based on avoidable and unavoidable exergy destruction concepts.

收藏
DataCite Commons2020-09-18 更新2025-04-16 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0019111&DOCBASE=IFD_REFDOC_EN&SETLANGUAGE=EN
下载链接
链接失效反馈
官方服务:
资源简介:
In this paper, the actual feasible reduction in the inefficiencies occurring in two different commercial CO2 refrigeration systems was evaluated. The analysis was based on the calculation of the avoidable and unavoidable irreversibilities taking place in their components. The systems under investigation, which were a R744 refrigeration system with parallel compression and a R744 refrigerating plant with dedicated mechanical subcooling, were assessed by taking into account the design outdoor temperature of 30 °C. A cooling capacity of 100 kW and an evaporating temperature of -10 °C were selected, while the global efficiencies of all the chosen compressors were obtained by using some manufacturers’ selection software. The results revealed that, in both the selected cases, over 60% of the irreversibilities could be brought down. In particular, the inefficiencies of all the compressors were almost totally avoidable, whereas only half of the exergy destruction related to both the gas coolers and the evaporators could be actually reduced. The auxiliary compressor and the subcooling loop were accountable for14.6% and 25% of the total avoidable inefficiencies associated with their corresponding cycles.
提供机构:
International Institute of Refrigeration (IIR)
创建时间:
2016-12-06
二维码
社区交流群
二维码
科研交流群
商业服务