Evaluation of the system and compressor reliability.
收藏DataCite Commons2020-09-18 更新2025-04-16 收录
下载链接:
http://www.iifiir.org/clientBookline/service/reference.asp?INSTANCE=EXPLOITATION&OUTPUT=PORTAL&DOCID=IFD_REFDOC_0015017&DOCBASE=IFD_REFDOC_EN&SETLANGUAGE=EN
下载链接
链接失效反馈官方服务:
资源简介:
Recently, low global warming potential (GWP) refrigerants have attracted attention as an alternative to the most commonly used refrigerants. We considered R32 as an alternative to R410A because of its low GWP and energy saving characteristics. This study focused on the selection of a suitable refrigeration oil for R32 that would not compromise compressor reliability. We found R32 to be poorly miscible with refrigeration oils used for R410A. This, combined with a higher discharge gas temperature for R32 compared to R410A, would result in lower compressor reliability. We selected a refrigeration oil suitable for R32 and confirmed compressor reliability equivalent to R410A.
提供机构:
International Institute of Refrigeration (IIR)
创建时间: